This manual also contains all user-pertinent specifications and semiconductor fusing recommendations. Refer to national and local electrical code safety guidelines whenever you install electrical equipment. The Watlow DIN-A-MITE power controller includes single-phase, 3-phase, 2-leg, and 3. View and Download Watlow DIN-A-MITE Style A user manual online. Solid-State Power Controller Style A. DIN-A-MITE Style A Controller pdf manual download. Also for: Din-a-mite series.

WATLOW DIN-A-MITE Style C User's Manual

General Specifications

Operator Interface
• Command signal input and indication light
• Alarm output and indication light
• Current limit indication LED

Amperage Rating

See the output rating curve chart on page 5 for all

the natural convection, fan-cooled, and through-
wall mount models.

Ratings are into a resistive heater load

• Maximum surge current for 16.6 milliseconds, 1,350 A

peak

User

• Maximum I

2

t for fusing is 9100 A

2

s

Watlow Din-a-mite C

• Latching current: 500mA minimum
• Holding current: 200mA minimum
• Fan current: 0.14 A for 24V

Î

(dc); 0.12 A for 120V

Å

(ac); 0.06A for 240V

Å

(ac)

• Off-state leakage 1mA at 25°C (77°F) maximum
• Power dissipation is 1.2 watts per amp switched

per controlled leg.

• 200KA SCCR type 1 and 2 approved with the

recommended fusing (see page 4)

Line Voltage
• 24 to 48V

Å

(ac) units: 20V

Å

minimum to 53V

Å

maximum

• 120 to 240V

Å

(ac) units: 48V

Å

minimum to 265V

Å

maximum

• 277 to 600V

Å

(ac) units: 85V

Å

minimum to 660V

Watlow Din A Mite C User Manual Pdf

Å

maximum

Alarms (zero cross models only)

Shorted SCR Alarm Option

• Alarm state when the input command signal is off and

a 10 A or more load current is detected by the current
transformer (two turns required for 5 A or three turns
for 2.5 A).

Open Heater Alarm Option

• Alarm state when the input command signal is on and

the load current detected by the current transformer is
less than the alarm set point. Available with Input
Control Signal option S only.

Alarm Output

• Energizes on alarm, non-latching
• Triac 24 to 240V

Å

(ac), external supply with a current

rating of 300 mA @ 25°C (77°F), 200mA @ 50°C
(122°F), 100mA @ 80°C (176°F) and a holding current
of 200 µA with a latching current of 5mA typical.

Agency Approvals
• CE with proper filter:

2004/108/EC Electromagnetic Compatibility Directive

EN 61326: Industrial Immunity Class A emissions
Not suitable for Class B environments.

2006/95/EC Low Voltage Directive

EN 50178 Safety Requirements
Installation category III, Pollution degree 2

Phase angle and phase angle with current limit Input

Control Signal Types (P and L) are not CE approved.

• UL

®

Anker powercore 15000 redux user manual. What you get: Power core 15000 redox portable charger, Micro USB cable (USB-C cable and Lightning cable not included), travel pouch, welcome guide, our worry-free 18-month, and customer service.

50 Type 4X Enclosure and UL ANSI/ISA 12.12.01

Temperature Code T4A

The through-wall heatsink package is suitable for use in

Class I, Division 2 Groups A, B, C and D Hazardous
Locations or unclassified or non-hazardous locations.

ç

Watlow

WARNING – EXPLOSION HAZARD

SUBSTITUTION OF ANY COMPONENTS MAY IMPAIR
SUITABILITY FOR CLASS I, DIVISION 2.

ç

WARNING – EXPLOSION HAZARD

DO NOT DISCONNECT WHILE THE CIRCUIT IS
LIVE OR UNLESS THE AREA IS KNOW TO BE FREE
OF IGNITIBLE CONCENTRATIONS.

UL

®

508 listed and C-UL

®

, File E73741

• Shock and vibration tested to IEC 60068-2-32
• Vibration tested to IEC 60068-2-6

Input Terminals
• Compression: Will accept 0.2 to 1.5 mm

2

(24 to 16

AWG) wire

• Torque to 0.5 Nm (4.4 in-lb) with a 3.5 mm (1/8 in)

blade screwdriver

• Wire strip length 5.5 mm (0.22 in)

Line, Load and Ground Terminals
• Compression: Will accept 2.5 to 25 mm

2

(14 to 3 AWG)

wire

• Torque to 2.7 Nm (24 in-lb) with a 6.4 mm (1/4 in)

blade screwdriver, or a Type 1A #2 Pozi driver.

• Retorque after 48 hours to minimize wire cold flow.
• Retorque line and load terminals every 3 to 6 months.
• Wire strip length 11 mm (7/16 in)

Operating Environment
• See the output rating curve chart on page 5.
• 0 to 90% RH (relative humidity), non-condensing
• Storage temperature: -40 to +85°C (-40 to 185°F)
• Insulation only tested to 3,000 meters

DIN Rail Mount
• DIN EN 50022, 35 by 7.5 mm
• Minimum clipping distance: 34.8 mm (1.37 in)
• Maximum clipping distance: 35.3 mm (1.39 in)

Back Panel Mount
• Four mounting holes M4 (No. 8) fastener

Through-Wall Mount
• See page 8 for through-wall cutout

NOTE: Mount cooling fins vertically. Cooling fan power
terminals: quick connect, 1/8' push on, 16-14 AWG wire.
Amp part no. 640929-1 or equivalent

Weight
• 1.0 to 1.9 kg (2.2 to 4.2 lb) depending upon model

Specifications are subject to change without notice.

Advertising
Popular Brands
Popular manuals

Din-a-mite, Din-a-mite solid-state power controller, User’s manual

Advertising

DIN-A-MITE

®

Style C

Solid-State Power Controller

User’s Manual

For good measure, I really reccomend you run your MP3 player through one of channels with the little red and white RCA connectors?, with a little extra bass, a little less mid, and a little extra top, trust me! https://nindatabase.netlify.app/dynacord-powermate-1000-3-user-manual.html.

DIN-A-MITE Solid-State Power Controller

0600-0025-0009 Rev N

Made in the U.S.A.

September 2013

Please consult this user’s manual when you
place your new DIN-A-MITE into service. It
contains all the necessary information to mount
and wire the product into the application. This
manual also contains all user-pertinent
specifications and semiconductor fusing
recommendations. Refer to national and local
electrical code safety guidelines whenever you
install electrical equipment.

The Watlow DIN-A-MITE power controller
includes single-phase, 3-phase, 2-leg, and 3-
phase, 3-leg, 120 to 600V

Å (ac) operation.

Current switching capabilities range from 30 to

80A, depending on the model ordered. See the
output rating curves.

Zero-cross variable time base or V

‡ (ac/dc) input

contactor versions are available. Shorted SCR
(silicon controlled rectifier) and open-heater
protection is available on some zero-cross
models. Phase angle and phase angle with
current limit is also available on single-phase
models. The model number indicates the power
controller’s configuration.

The DIN-A-MITE power controller is designed and
manufactured by Watlow in Winona, Minnesota.

1241 Bundy Boulevard, Winona, Minnesota USA 55987

Phone: +1 (507) 454-5300, Fax: +1 (507) 452-4507 http://www.watlow.com