Publication 1609-PP005A-EN-P – February 2013 Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.
Input
V nom. 120V
Capacity
600N 600VA (390 W)
1000N 1000VA (650 W)
1500N 1500VA (980 W)
Voltage Range, default 90~145V
Voltage Range, widest, on line 90~145V
Current nom. 5.5A
Capacity Frequency 50/60Hz±3Hz
PFC
None (Load power factor is
refl ected in the input line
current)
Output
V nom. 120V
Capacity
600N 600VA (390 W)
1000N 1000VA (650 W)
1500N 1500VA (980 W)
On Line
Output Range, default 108~132V
Output Voltage Range, widest 108~132V
Transfer Point Accuracy ±3%
On Battery
V nom. 120V (Sine Wave)
Frequency 50/60Hz ±0.5Hz (Factory Default: 60Hz ±0.5Hz)
THD ≦10% (Full Linear Load)
Short Circuit Protection
Crest Factor 2.2:1
Effi ciency
On Battery 75% (Typical with resistive load)
On Line 86% (Typical with resistive load excluding AVR mode)
Protection
Surge 380 Joules (Total Performance Rated With 10*1000ms Pulse)
Overload
>110-130% Shutdown after 10 Seconds
>130% Shutdown immediately
Output Short On Line Premises branch circuit over-current protection
Output Short On Battery Shutdown
Thermal Protection UPS inside temperature 60 degree C
Bypass N/A
Regulatory
Safety UL1778, CSA C22.2 No. 107.3-05, EN/IEC62040-1
EMC FCC & CE (Class A)
Markings UL, cUL, FCC, CE
Battery Pack
Run Time ≧5 Minutes (at 25 degree C, full R load)
Type Sealed Lead Acid Battery
Rated
Capacity
0-40°C:
B.B. BP5-12
12V/5.5Ah
0-50°C:
B.B. HRL5.5-12
Charger Current limited, constant voltage fl oat charger
Recharge Time Less than 8 hours to 90% capacity after discharged with full load
Lifetime 2~3 years @ 25 degree C ambient
Allen Bradley 1609 Ups
Environmental
Operating Temperature –
Standard Battery
0°C~40°C (32°F~104°F)
0°C~50°C (32°F~122°F)
Operating Temperature –
Hi Temperature Battery 0°C~50°C (32°F~122°F)
Storage Temperature – 15…45°C (5°F…113°F)
Altitude Operating 0 … 6600 feet (0 to 2000 meters)
Humidity Operating/Storage 5~95 % RH (Non-condensing)
Heat
Output
On Line, Full
load: 217 BTU per hour
On Line, Full
load, Charging: 296 BTU per hour
On Battery: Full
Load: 1331 BTU per hour
Audible
Noise 50 dBA at front side one meter
Panel Mount Integrated Dry I/O Contacts
Remote
On/Off
Replaceable
Surge
Protection
EtherNet/IP USB AVR Expandable Battery
1609-B • • • • •
1609-D • • • • • • • •
1609 N600D-
Bulletin
1609
Product Family
D= Deluxe (Full featured)
B= Basic
VA (Volt-Amperes)
600= 600 VA
1000 = 1000 VA
1500 = 1500 VA
Voltage
N = 120VAC
Input/Output
Batteries not included:
1609-B units require two batteries.
1609-D units require three batteries.
Standard battery is 1609-SBAT.
Hi-Temp Battery is 1609-HBAT.
Bulletin 1609
Next Generation Industrial UPS
Faster Recovery From Power Failures
An industrial uninterruptable power supply (UPS) can enable your
production production process to recover quickly from a line power
interruption, saving you lost production time and work in process.
Sometimes users think that because there isn’t a battery large enough
to keep the process itself going, a UPS won’t make any diff erence. What
a UPS can do eff ectively, is to keep the control system, networks and
sensors powered, so when power returns, the control system knows where
everything is and can start up without having to completely reset and clear
the work in process.
The 1609 is uniquely designed for the industrial market to provide back-up
AC power to the control cabinet. The 1609 will provide back-up power to
bridge dips, sags, or brief losses of power. If necessary, the 1609 will facilitate
a safe shut-down of your industrial PC, PLC, data logging HMI, or any other
critical device in the control scheme. Without a 1609 in place, the customer
is faced with nuisance power dips, ex¬tended down-time, and potential
machine damage; all of which can result in signifi ¬cant and costly challenges
The newer technologies of industrial controls are much more sensitive to
power fl uctuations, the need for clean consistent reliable power continues
to grow as industrial automation and process control continues to migrate
more towards more sensitive electronic controls and extensive networking.
Industrial UPS products are about increasing system reliability and
minimizing down time due to power disruptions and product failures in the
control system.
Features and Benefi ts
The 1609 family of Industrial
Uninterruptible Power Supplies is
designed for industrial applications –
with features required for remote control
and operation inside of industrial
control panels.
DIN-rail/panel/fl oor mount
• Flexibility to meet most installation
scenarios, included control panels
typically used in production
environments.
Hard-wired input and output
• Electrical codes typically do not allow
plug-in connections within a control
panel.
Integrated remote on/off and
Dry I/O contacts
• Meet code requirements to allow
proper shutdown of the UPS when
control panel is open and closed an
provide for remote monitoring and
control of UPS.
d
USB communications
• Provides remote monitoring and
confi guration through included
software
True sine wave AC output
• Compatible with the widest range of
equipment.
Expandable battery capacity
• Additional batteries can be added
to the UPS to extend run-time or
accommodate additional equipment.
(1609-D Only)
Ups User Employee
EtherNet/IP communications
• Allows the ability to communicate
with and integrate to Rockwell
Automation Integrated Architecture.
(Optional, for 1609-D Only)
Batteries not included:
1609-B units require two batteries.
Allen Bradley 1609-d Ups Manual
1609-D units require three batteries.
My Ups User Id
Standard battery is 1609-SBAT.
My Ups User
Hi-Temp Battery is 1609-HBAT.