Allen Bradley 1609-d Ups User Manual

Shutdown Management Software For Windows User Manual. Contact your local Allen-Bradley distributor. Manage your Uninterruptible Power Supply (UPS).

Allen-Bradley, LISTEN. THINK. SOLVE. and Rockwell Software are trademarks of Rockwell Automation, Inc.

  • View and Download Allen-Bradley Bulletin 1609 user manual online. Bulletin 1609 Uninterruptible Power Supply. Bulletin 1609 UPS pdf manual download. Also for: 1609-d, 1609-b.
  • This banner text can have markup. Search the history of over 384 billion web pages on the Internet.

Trademarks not belonging to Rockwell Automation are property of their respective companies.

Publication 1609-PP005A-EN-P – February 2013 Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.

Input

V nom. 120V

Capacity

600N 600VA (390 W)

1000N 1000VA (650 W)

1500N 1500VA (980 W)

Voltage Range, default 90~145V

Voltage Range, widest, on line 90~145V

Current nom. 5.5A

Capacity Frequency 50/60Hz±3Hz

PFC

None (Load power factor is

refl ected in the input line

current)

Output

V nom. 120V

Capacity

600N 600VA (390 W)

1000N 1000VA (650 W)

1500N 1500VA (980 W)

On Line

Output Range, default 108~132V

Output Voltage Range, widest 108~132V

Transfer Point Accuracy ±3%

On Battery

V nom. 120V (Sine Wave)

Frequency 50/60Hz ±0.5Hz (Factory Default: 60Hz ±0.5Hz)

THD 10% (Full Linear Load)

Short Circuit Protection

Crest Factor 2.2:1

Effi ciency

On Battery 75% (Typical with resistive load)

On Line 86% (Typical with resistive load excluding AVR mode)

Protection

Surge 380 Joules (Total Performance Rated With 10*1000ms Pulse)

Overload

>110-130% Shutdown after 10 Seconds

>130% Shutdown immediately

Output Short On Line Premises branch circuit over-current protection

Output Short On Battery Shutdown

Thermal Protection UPS inside temperature 60 degree C

Bypass N/A

Regulatory

Safety UL1778, CSA C22.2 No. 107.3-05, EN/IEC62040-1

EMC FCC & CE (Class A)

Markings UL, cUL, FCC, CE

Battery Pack

Run Time 5 Minutes (at 25 degree C, full R load)

Type Sealed Lead Acid Battery

Rated

Capacity

0-40°C:

B.B. BP5-12

12V/5.5Ah

0-50°C:

B.B. HRL5.5-12

Charger Current limited, constant voltage fl oat charger

Recharge Time Less than 8 hours to 90% capacity after discharged with full load

Lifetime 2~3 years @ 25 degree C ambient

Allen Bradley 1609 Ups

Environmental

Operating Temperature –

Standard Battery

0°C~40°C (32°F~104°F)

0°C~50°C (32°F~122°F)

Operating Temperature –

Hi Temperature Battery 0°C~50°C (32°F~122°F)

Storage Temperature – 15…45°C (5°F…113°F)

Altitude Operating 0 … 6600 feet (0 to 2000 meters)

Humidity Operating/Storage 5~95 % RH (Non-condensing)

Heat

Output

On Line, Full

load: 217 BTU per hour

On Line, Full

load, Charging: 296 BTU per hour

On Battery: Full

Load: 1331 BTU per hour

Audible

Noise 50 dBA at front side one meter

Panel Mount Integrated Dry I/O Contacts

Remote

On/Off

Replaceable

Surge

Protection

EtherNet/IP USB AVR Expandable Battery

1609-B • • • • •

1609-D • • • • • • • •

1609 N600D-

Bulletin

1609

Product Family

D= Deluxe (Full featured)

B= Basic

VA (Volt-Amperes)

600= 600 VA

1000 = 1000 VA

1500 = 1500 VA

Voltage

N = 120VAC

Input/Output

Batteries not included:

1609-B units require two batteries.

1609-D units require three batteries.

Standard battery is 1609-SBAT.

Hi-Temp Battery is 1609-HBAT.

Bulletin 1609

Next Generation Industrial UPS

Faster Recovery From Power Failures

An industrial uninterruptable power supply (UPS) can enable your

production production process to recover quickly from a line power

interruption, saving you lost production time and work in process.

Sometimes users think that because there isn’t a battery large enough

to keep the process itself going, a UPS won’t make any diff erence. What

a UPS can do eff ectively, is to keep the control system, networks and

sensors powered, so when power returns, the control system knows where

everything is and can start up without having to completely reset and clear

the work in process.

The 1609 is uniquely designed for the industrial market to provide back-up

AC power to the control cabinet. The 1609 will provide back-up power to

bridge dips, sags, or brief losses of power. If necessary, the 1609 will facilitate

a safe shut-down of your industrial PC, PLC, data logging HMI, or any other

critical device in the control scheme. Without a 1609 in place, the customer

is faced with nuisance power dips, ex¬tended down-time, and potential

machine damage; all of which can result in signifi ¬cant and costly challenges

The newer technologies of industrial controls are much more sensitive to

power fl uctuations, the need for clean consistent reliable power continues

to grow as industrial automation and process control continues to migrate

more towards more sensitive electronic controls and extensive networking.

Industrial UPS products are about increasing system reliability and

minimizing down time due to power disruptions and product failures in the

control system.

Features and Benefi ts

The 1609 family of Industrial

Uninterruptible Power Supplies is

designed for industrial applications –

with features required for remote control

and operation inside of industrial

control panels.

DIN-rail/panel/fl oor mount

• Flexibility to meet most installation

scenarios, included control panels

typically used in production

environments.

Hard-wired input and output

• Electrical codes typically do not allow

plug-in connections within a control

panel.

Integrated remote on/off and

Dry I/O contacts

• Meet code requirements to allow

proper shutdown of the UPS when

control panel is open and closed an

provide for remote monitoring and

control of UPS.

d

USB communications

• Provides remote monitoring and

confi guration through included

software

True sine wave AC output

• Compatible with the widest range of

equipment.

Expandable battery capacity

• Additional batteries can be added

Allen

to the UPS to extend run-time or

accommodate additional equipment.

(1609-D Only)

Ups User Employee

EtherNet/IP communications

• Allows the ability to communicate

with and integrate to Rockwell

Automation Integrated Architecture.

(Optional, for 1609-D Only)

Batteries not included:

1609-B units require two batteries.

Allen Bradley 1609-d Ups Manual

1609-D units require three batteries.

My Ups User Id

Standard battery is 1609-SBAT.

My Ups User